IS 4031:1988 Part 6 is the Indian Standard (BIS) for methods of physical tests for hydraulic cement - part 6: determination of specific gravity. This part of the standard covers the method for determining the specific gravity of hydraulic cement. It details the Le Chatelier flask testing procedure, which measures the volume of a non-reactive liquid displaced by a known mass of cement.
Describes the procedure for determining the specific gravity of hydraulic cement using a Le Chatelier flask.
Key reference values — verify against the current code edition / project specification.
| Reference | Value | Clause |
|---|---|---|
| Determines | Specific gravity of cement (Le-Chatelier flask) | Scope |
| Typical OPC | ≈ 3.15 (fresh) | Rule |
| Liquid | Kerosene (non-reactive) — NEVER water | Critical |
| Mix-design use | Required by IS 10262 absolute-volume method | Application |
| Condition check | Low SG → moisture-degraded / air-set cement | Concept |
| Don't | Assume 3.15 for a stored/suspect cement — measure | Caution |
| Not | = bulk/unit density (that is Part 11) | Caution |
IS 4031 Part 6:1988 is the method for determining the specific gravity of hydraulic cement (Le-Chatelier flask, with a non-reactive liquid such as kerosene). Specific gravity (~3.15 for OPC) is a small but foundational input: it is required by IS 10262 concrete mix design (absolute-volume method) and is an early indicator of cement condition.
It sits in the cement-testing stack:
Specific gravity is the ratio of cement mass to the mass of an equal volume of water, measured by displacement of a non-reactive liquid in a Le-Chatelier flask:
The engineering point: SG is a humble number but it is *used*, in mix design and as a quick degradation check. Assuming a textbook 3.15 for a stored or suspect cement, or running the test with water, are the ways it goes wrong — and the error propagates quietly into the mix proportions.
Scenario: establishing inputs for an IS 10262 mix and screening a stored cement.
Step 1 — non-reactive liquid: use kerosene in the Le-Chatelier flask (never water — it would hydrate the cement).
Step 2 — measure displacement: record the liquid level, add a known cement mass, record the new level → volume displaced.
Step 3 — compute SG: SG = cement mass / (volume displaced × density of water); fresh OPC ≈ 3.15.
Step 4 — use in mix design: feed the measured SG into the IS 10262 absolute-volume calculation — don't just assume 3.15 for a stored/suspect cement.
Step 5 — read as a condition check: a notably low SG → likely moisture-degraded / air-set cement → investigate further (setting/strength) before use.
The number is small but it both proportions the concrete and screens the cement — measured, not assumed, for any cement whose freshness is in doubt.
1. Assuming a textbook 3.15. Fine for fresh OPC in rough work, but a stored/suspect cement should be measured — the SG feeds mix proportions.
2. Using water instead of kerosene. Water hydrates the cement and corrupts the result — a non-reactive liquid is mandatory.
3. Ignoring SG as a condition indicator. A low SG is an early flag of moisture-degraded cement — don't discard the signal.
4. Confusing specific gravity with bulk density. SG is the particle ratio (for absolute-volume mix design); bulk/unit density is a different property.
5. Sloppy flask reading / temperature. Displacement is small — careless reading biases the SG and the downstream mix.
IS 4031 Part 6 is reaffirmed and produces one of the least-glamorous numbers in cement testing — yet it is actually used: the IS 10262 absolute-volume mix design needs the cement specific gravity, and a wrong SG quietly mis-proportions the concrete and its yield. The two practitioner habits: don't reflexively assume the textbook 3.15 for a stored or suspect cement (measure it — and read a low value as a degradation flag), and never run the test with water (kerosene only, or hydration corrupts it). It's a small measurement that does two useful jobs — proportioning the mix and screening the cement — and is best treated as a measured input, not a remembered constant, whenever cement freshness is in any doubt.
| Parameter | IS Value | International | Source |
|---|---|---|---|
| Test Temperature | 27 ± 2 °C | 23.0 ± 2.0 °C | ASTM C191-21 |
| Test Humidity (for specimens) | ≥ 90% RH | ≥ 95% RH | ASTM C191-21 |
| Initial Set Needle Cross-Section | 1 mm square | 1 mm diameter (circular) | ASTM C191-21 |
| Criterion for Initial Setting Time | Penetration to 5.0 ± 0.5 mm from mould bottom | Penetration to 25 ± 0.5 mm from surface | ASTM C191-21 |
| Criterion for Final Setting Time | Needle makes an impression, but annular attachment does not | Needle does not sink visibly into the paste | ASTM C191-21 |
| Mass of Cement for Test Paste | 400 g | 650 g | ASTM C191-21 |
| Mould Height | 40 ± 0.2 mm | 40 ± 1 mm | ASTM C191-21 |