Register · FMT-MEP-010

IR (Insulation Resistance) Test Register

7 fields across 3 sections. Pre-commissioning + periodic maintenance test — life-safety + insurance critical.
7 Fields
3 Sections
Pre-commissioning + annual
Electrical Engineer, Maintenance

Format Preview

S.No.Field / CheckpointReferenceStatus
A. CIRCUIT IDENTIFICATION
A1Circuit no. + location + cable size + length
Acceptance: Per drawing
Per cable schedule
OK
NC
NA
A2Test date + tester (megger model + voltage)
Acceptance: Per voltage class
Megger 500V / 1000V / 2500V
OK
NC
NA
B. TEST PROCEDURE + RESULTS
B1Insulation resistance phase-to-phase (R-Y, Y-B, R-B)
Acceptance: Per code
≥ 1 MΩ per IS 732
OK
NC
NA
B2Insulation resistance phase-to-earth (each phase)
Acceptance: Per code
≥ 1 MΩ
OK
NC
NA
B3Reading at 1 minute + 10 minute (Polarisation Index PI = 10min/1min)
Acceptance: Computed
PI ≥ 2 indicates good
OK
NC
NA
C. ACCEPTANCE
C1Pass / Fail per circuit
Acceptance: Logged
Below 1 MΩ → reject + investigate
OK
NC
NA
C2Annual re-test for fixed wiring (LV) / 5-yearly for industrial
Acceptance: Year tested
Per maintenance schedule
OK
NC
NA
A. CIRCUIT IDENTIFICATION
A1Circuit no. + location + cable size + length
Per cable schedule
Per drawing
OKNCNA
A2Test date + tester (megger model + voltage)
Megger 500V / 1000V / 2500V
Per voltage class
OKNCNA
B. TEST PROCEDURE + RESULTS
B1Insulation resistance phase-to-phase (R-Y, Y-B, R-B)
≥ 1 MΩ per IS 732
Per code
OKNCNA
B2Insulation resistance phase-to-earth (each phase)
≥ 1 MΩ
Per code
OKNCNA
B3Reading at 1 minute + 10 minute (Polarisation Index PI = 10min/1min)
PI ≥ 2 indicates good
Computed
OKNCNA
C. ACCEPTANCE
C1Pass / Fail per circuit
Below 1 MΩ → reject + investigate
Logged
OKNCNA
C2Annual re-test for fixed wiring (LV) / 5-yearly for industrial
Per maintenance schedule
Year tested
OKNCNA
Approval / Sign-Off
APPROVED
HOLD — REVISIONS REQUIRED
REJECTED
Overall Verdict
Name / Sign / Date
Prepared By — Name / Sign
Name / Sign / Date
Reviewed By — Name / Sign
Name / Sign / Date
Approved By — Name / Sign
Name / Sign / Date
Date & Time
Name / Sign / Date
Remarks
Name / Sign / Date

Engineer's Notes — IR (Insulation Resistance) Test Register

Why the IR Test Register matters

Insulation Resistance (IR) Test verifies that the insulation between electrical conductors + earth is adequate — preventing short circuits, electrical fires, and personal shock. For every cable, every motor winding, every electrical panel installed on-site, IR must be tested before commissioning + recorded.

Governing standards: IS 732:2019 (Code of Practice for Electrical Wiring Installations), IS 3043:2018 (Code of Practice for Earthing), CEA Regulations 2010. Without an IR Test Register, electrical compliance is unverifiable; statutory electrical inspector cannot approve installation.

IR test methodology + acceptance

Equipment: 500V or 1000V or 2500V DC megger (Megohmmeter); higher test voltage for higher rated cables.

Test conditions: - Apply test voltage between live conductor + earth - Hold for minimum 60 seconds - Record resistance value in megohms (MΩ) - Test between phase-to-phase + phase-to-neutral + each phase-to-earth

Acceptance criteria (per IS 732): - LV cables (≤ 1.1 kV): ≥ 1 MΩ per kV of voltage; minimum 1 MΩ - MV cables (3.3-33 kV): ≥ 100 MΩ-km (megohms × km of cable length) - HV cables (66 kV+): ≥ 1000 MΩ-km - Motor windings (newly installed): ≥ 100 MΩ - Switchboards / panel boards: ≥ 100 MΩ each circuit

Test frequency: - Pre-commissioning: 100% of installation; mandatory - Annual maintenance: rolling per equipment - Post-fault: when fault occurred; verify integrity post-repair - Post-modification: after any wiring change

Documentation: equipment ID + location, test voltage, IR value, ambient temperature (affects readings), date, tester signature, equipment calibration ref.

Common IR-test issues

1. Test voltage wrong — using 500V megger on 11kV cable; reading meaningless. Match megger voltage to cable rating. 2. No temperature compensation — IR varies with temperature (higher temp = lower resistance). Specify ambient + apply correction factor. 3. Test not held long enough — short test (5-10s) reads transient + lower than actual; minimum 60s required. 4. Equipment energised during test — dangerous + invalid results. Isolate + earth before testing. 5. No baseline / trend — annual readings without baseline don't reveal gradual degradation. 6. Connection corrosion — bad megger probe contact gives high reading (apparent good insulation); verify probe. 7. Damaged cable not retested after repair — repair completed; IR test missed. 8. No statutory inspector certification — large installations need Electrical Inspector approval; without IR Register, inspector won't certify.

Cross-references

Companion formats: - Earthing Test Register (FMT-MEP-009) — earthing resistance verification - MEP cable schedule (BOQ + installation tracking) - Statutory electrical inspector approval certificates

Codes + standards: - IS 732:2019 — Code of practice for electrical wiring installations - IS 3043:2018 — Code of practice for earthing - IS 7098 (Parts 1-4) — XLPE cables for various voltages - IS 1554 (Parts 1-2) — PVC insulated cables - IS 13947 series — Low voltage switchgear - CEA (Measures Relating to Safety + Electric Supply) Regulations 2010 - NEC 2023 — National Electrical Code India