BOQ Builder·Auto-BOQ from dimensions, DSR ratesNEWBidEasy·Government tenders, searchableLIVEInfraLens App·Free on Play Store, offline-readyNEW
Formats  › MEP Testing & Commissioning  › Cable Schedule
Schedule · FMT-MEP-008

Cable Schedule

9 fields across 3 sections. Cable schedule — every cable on site is tracked here for maintenance + fault tracing.
9 Fields
3 Sections
Per panel / circuit
Electrical Engineer

Format Preview

S.No.Field / CheckpointReferenceStatus
A. CABLE IDENTIFICATION
A1Cable tag no. + from + to + length
Acceptance: Per drawing
Per drawing
OK
NC
NA
A2Cable size + type (PVC / XLPE / FRLS) + cores
Acceptance: Per design
Per current + voltage drop calculation
OK
NC
NA
A3Voltage rating (1100V / 3.3kV / 11kV)
Acceptance: Per spec
Per system voltage
OK
NC
NA
B. INSTALLATION + TESTING
B1Route — tray / conduit / direct buried / through wall
Acceptance: Verified
Per drawing
OK
NC
NA
B2Insulation Resistance (IR) test — pass / fail
Acceptance: Megger test logged
≥ 1 MΩ at 500/1000V megger per IS 732
OK
NC
NA
B3Continuity test
Acceptance: Logged
Open / short / earth fault test
OK
NC
NA
B4HV test (for MV/HV cables) — voltage withstand
Acceptance: Per cable class
Per IS 7098
OK
NC
NA
C. TERMINATION
C1Termination quality — lugs, glands, ferrules, labels
Acceptance: Inspected
Per IS 9000
OK
NC
NA
C2Earthing — armour to earth at one end (per IS 3043)
Acceptance: Per spec
Per code
OK
NC
NA
A. CABLE IDENTIFICATION
A1Cable tag no. + from + to + length
Per drawing
Per drawing
OKNCNA
A2Cable size + type (PVC / XLPE / FRLS) + cores
Per current + voltage drop calculation
Per design
OKNCNA
A3Voltage rating (1100V / 3.3kV / 11kV)
Per system voltage
Per spec
OKNCNA
B. INSTALLATION + TESTING
B1Route — tray / conduit / direct buried / through wall
Per drawing
Verified
OKNCNA
B2Insulation Resistance (IR) test — pass / fail
≥ 1 MΩ at 500/1000V megger per IS 732
Megger test logged
OKNCNA
B3Continuity test
Open / short / earth fault test
Logged
OKNCNA
B4HV test (for MV/HV cables) — voltage withstand
Per IS 7098
Per cable class
OKNCNA
C. TERMINATION
C1Termination quality — lugs, glands, ferrules, labels
Per IS 9000
Inspected
OKNCNA
C2Earthing — armour to earth at one end (per IS 3043)
Per code
Per spec
OKNCNA
Approval / Sign-Off
APPROVED
HOLD — REVISIONS REQUIRED
REJECTED
Overall Verdict
Name / Sign / Date
Prepared By — Name / Sign
Name / Sign / Date
Reviewed By — Name / Sign
Name / Sign / Date
Approved By — Name / Sign
Name / Sign / Date
Date & Time
Name / Sign / Date
Remarks
Name / Sign / Date

Engineer's Notes — Cable Schedule

Why the Cable Schedule matters

On any non-trivial electrical installation — commercial building, hospital, industrial plant, infrastructure project — there are hundreds to thousands of individual cables routed between sources, distribution panels, sub-distribution boards, motor control centres, equipment, and loads. Each cable has its own: - Source + destination (FROM / TO) - Length (m) - Size + cores (e.g., 4 × 35 sq mm Cu) - Type (PVC / XLPE / FRLS / FRLSZH) - Voltage rating (1.1 kV / 3.3 kV / 11 kV / 33 kV) - Routing (tray / conduit / direct buried / through wall) - Tests + commissioning status

The Cable Schedule is the master index that tracks every single cable. Without it: - Maintenance impossible — fault on Cable X; no record of size / route / termination; trace from scratch (hours of detective work) - As-built documentation incomplete — handover to client / FM has gaps - No commissioning verification — was insulation tested? Was continuity verified? - AMC dispute — vendor refuses warranty without proof of as-installed configuration

Governed by IS 732:2019 (Electrical Wiring Installation Code) + IS 1554 Part 1 (PVC cable specification) + IS 7098 (XLPE cable specification) + IS 3043 (earthing) + National Electrical Code (NEC) 2023 + CEA Safety + Electric Supply Regulations 2010.

What the cable schedule captures

Per-cable record:

Cable identification: - Cable tag number (project-specific, e.g., CB-MDB-LP01) - FROM: source equipment (e.g., Main DB) - TO: destination equipment (e.g., Lighting Panel 01) - Length (m)

Cable specification: - Size: cross-sectional area per phase (e.g., 4 × 50 sq mm Cu) - Cores: number of conductors (2C / 3C / 4C / 5C) - Conductor material: Copper (Cu) or Aluminium (Al) - Insulation type: - PVC (most common, 70°C) per IS 1554 - XLPE (Cross-linked Polyethylene, 90°C) per IS 7098 — preferred for higher capacity - FRLS (Fire Retardant Low Smoke) per IS 10810 — for fire-critical areas - FRLSZH (Halogen-free) — for sensitive locations - Mineral insulated (fire-survival) — for emergency circuits per IS 14697 - Armouring: Armoured / Un-armoured (galvanised steel wire / strip) - Outer sheath: PVC / FR / FRLS - Voltage rating: - 1.1 kV: LT (general distribution) - 3.3 kV: medium voltage - 11 kV / 22 kV / 33 kV / 66 kV: HV / EHV

Installation details: - Routing: ladder tray / perforated tray / conduit (PVC / GI) / direct buried / through wall - Spacing: from other cables (per IS 732 for de-rating) - Bend radius: minimum per cable spec (typically 12-15× OD for power) - Fixing: cable cleats / saddles / strain reliefs - Penetrations: fire-stopped per IS 16092 (or equivalent) - Marking: tags every 10 m + at every termination

Termination details: - End A (FROM): cable gland + lug + ferrule + label - End B (TO): same - Gland type: A2 / E1W / CW (per IS 12943) - Lug type: copper crimped / soldered - Earth connection: armour earthed at one end (per IS 3043) - Color coding: per IEC 60446 — phase / neutral / earth

Testing + commissioning: - Continuity test: each conductor end-to-end - Insulation Resistance (IR) test: - 500V megger for LT cables; ≥ 1 MΩ minimum (per IS 732) - 1000V or 2500V for HT cables; per cable spec - HV withstand test for MV/HV cables (per IS 7098): - 3.5 × Uo for 5 minutes typically - Pass = no breakdown - Earth continuity test - Phase rotation check (3-phase loads) - Voltage drop measurement on energisation

Documentation: - Cable tested + date + tester - Test certificates filed - As-built routing updated - Termination photos

Sample cable sizing thumb rules (3-phase, copper, 415V): - 6 sq mm Cu: 40 A (15-25 m) - 16 sq mm Cu: 80 A (30-50 m) - 35 sq mm Cu: 140 A (50-75 m) - 70 sq mm Cu: 200 A (75-100 m) - 95 sq mm Cu: 240 A - 150 sq mm Cu: 310 A - 240 sq mm Cu: 400 A - 300 sq mm Cu: 460 A - 500 sq mm Cu: 620 A - Always verify with voltage drop calculation: ΔV ≤ 3% from source to last load

Common cable schedule failures

1. Tag system inconsistent — different parts of project use different naming; later confusion.

2. Cable size wrong — voltage drop > 3%; equipment under-voltage; nuisance trips.

3. PVC used in fire-critical area — should be FRLS / FR; non-compliance with NBC Part 4.

4. Armour earthed at both ends — induced currents flow; cable heats up + corrosion; should be earthed at one end only.

5. Voltage rating wrong — 1.1 kV cable on 3.3 kV system; insulation breakdown.

6. De-rating not applied — multiple cables in one tray (close packing); current capacity reduces; not corrected.

7. Bend radius violated — sharp bends at trays / pulls; conductor strain; later failure.

8. IR test on energised cable — should be done before energisation; sometimes done after; result irrelevant.

9. HV test skipped — for HT cables; defects not detected; first energisation = catastrophic failure.

10. Lug crimping wrong — wrong die used; loose connection; arcing + heat + fire risk.

11. Termination labels missing — no tag at panel; fault tracing impossible; FM frustration.

12. Continuity test perfunctory — only one conductor; should be each.

13. Test instruments uncalibrated — megger drift; results unreliable.

14. Penetrations not fire-stopped — through-wall openings without intumescent sealant; fire spread risk.

15. Buried cable without protection — direct buried without sand bedding + warning tape; later excavation damages cable.

16. As-built cable schedule not maintained — original schedule + site changes diverge; handover incomplete.

17. Multi-pulled cables — 3-4 cables pulled through single conduit; conduit fill exceeded; cables damaged during pull.

18. Voltage drop not verified at energisation — calculated OK but actual far load; cable adequacy questionable.

19. Junction boxes inadequate — cables joined without proper JB; future fault location impossible.

20. Cable trays overloaded — design for 60% fill; actual 90%+; heat + mechanical stress.

Cross-references

Companion formats: - Earthing Test Register (FMT-MEP-009) — earth + bonding - Single Line Diagram (SLD) — overall electrical scheme - Panel Schedules — distribution board details - Lighting Layout — light fixture circuits - DG Set T&C — emergency power - Substation T&C — HT side - Insulation Resistance Test Register - Material Test Report (FMT-STR-005) — cable MTC verification

Codes + standards: - IS 732:2019 — Code of Practice for Electrical Wiring Installations - IS 1554 Part 1:1988 — PVC Insulated Cables for 1100V - IS 7098 Part 1:1988 — XLPE Insulated Cables for 1100V - IS 7098 Part 2:2011 — XLPE Insulated Cables for 3.3 to 33 kV - IS 7098 Part 3:2017 — XLPE Insulated Cables for 66 kV + above - IS 10810 Parts 1-67 — Cable testing methods - IS 3043:2018 — Code of Practice for Earthing - IS 12943:1990 — Cable Glands - IS 16092 + IS 11530 — Fire safety for cables - IS 8130:2013 — Conductors for Insulated Electric Cables + Flexible Cords - National Electrical Code (NEC) 2023 — IS 732 + IS 3043 + IS 5216 integration - CEA Safety + Electric Supply Regulations 2010 — Sec 26-30 (Cabling + Wiring) - IEC 60502-1, IEC 60502-2 — International cable specs (referenced) - BS 7671 / IET Wiring Regulations — UK reference - NFPA 70 (US NEC) — American reference

More related